What Should Be Paid Attention To When Placing The Generator Set In The Machine Room
For built-in generator sets, due to the particularity of the performance of diesel generator sets, every detail of the machine room setting must be paid attention to. Such as: ventilation, cooling, site size, etc. inside the machine room. Now, let's take a look at some matters that should be paid attention to when the generator set equipment is built in the machine room with Huaquan Power:
1.the ground foundation requirements of the machine room:
The installation of the machine must be on a horizontal ground or a concrete ground with sufficient strength, and the general thickness should be greater than 200mm to ensure that the unit can be placed flat.
2.Pay special attention to the size of the generator room
At the beginning, some size considerations have been mentioned. Here, let me explain in depth:
After the unit is successfully installed, there must generally be enough space to accommodate the following equipment that you may want to place in the same room: generator set, daily fuel tank, unit-related control cabinet, parallel cabinet, etc. It is recommended that the unit should be installed in the machine room at least one meter away from any wall, box or control cabinet to facilitate daily inspection and maintenance of the unit.
3. Ventilation issues in the machine room
There must be enough fresh air in the machine room for diesel combustion and cooling of the unit. If necessary, ventilation ducts can be installed and a forced ventilation system can be used. The air inlet or exhaust area of the machine room should be at least twice the heat dissipation area.